Typical
Examples Of Fire Protection Using Cement Bonded Particleboard
Timber
Floors - 30 to 60 Minutes Fire Resistance To A Concealed
Grid Ceiling
1.Board
8mm-10mm standard C.P.Board fixed to grid at 300mm centres
using 18mm - 20mm No.8 self tapping screws.
2.
Flooring
Minimum 19mm tongue & groove C.P.Board or Chipboard.
3.
50mm nails at nominal 500mm centres.
4.
Insulation
50mm x 33kg/m3 cut and fixed tight between joists.
5.
Joist
Minimum 225mm x 38mm at maximum 610mm centres.
6.
Hangers fixed to joists at maximum 600mm centres
at least 100mm away from the bottom of joist with 50mm
nails.
7.
Don Fire Rated Grid
Concealed channel system 50mm x 26m with expansion couplings
at 3 mtrs with cross channels at board joints, fixed
to joist at 400mm centres 100mm up from base of joist.
For
full construction details and relevent data on the above
systems please contact Euroform
Products Limited.
| Contact
Us |
| Euroform Products
Ltd, |
The
Heliport, Lyncastle Road, Appleton, Warrington WA4 4SN |
|
| Tel: +44
(0) 1925 860999 |
Fax: +44
(0) 1925 860066 |
Email: sales@euroform.co.uk |
Site Map
Due
to our policy of continuous development we reserve the right to change
design and specifications without prior notice. Euroform Products Limited
does not accept responsibility for any loss as a result of any company
or person relying on material on this website, or for any mistakes. Although
every care is taken to ensure accuracy, this website is a general guide
and specific technical advice is recommended before proceeding with any
transaction. Specific fact sheets, or, technical advice is available from
Euroform technical department 01925 860999. Copying or reproducing any
part of this website in any manner is not permitted without prior written
consent from Euroform Products Limited. |
Registered Office: Euroform Products Limited, Hillsborough Works, Langsett Road, Sheffield, S6 2LW Registered Number: 2945504 |
|